start the operation, the louvre moves through one full cycle, and then swings automatically (if AUTO has been set using the remote control) or moves to the setting angle (if MANUAL has been set using the remote control). 3. When operation stops / When the OFF/ON button is pressed to stop the operation, the louvre moves through one full cycle, and then stops in the down position, regardless of the remote control setting. 4. When thermostat is off / When operation is stopped by the indoor thermostat, the louvre moves through one full cycle, and then stops in the horizontal position, regardless of the remote control setting. 25.13. Outdoor unit fan excess heat dissipation control 1. When the operation is stopped while the compressor is in operation, the outdoor fan will run at SUPER HI fan speed for approximately 60 seconds and then stops. 25.14. Discharge temperature control 1. Operation / When the discharge temperature sensor detects a temperature of 100°C or higher during cooling mode operation, the liquid bypass valve will be turned on. 2. Cancelling / When the discharge temperature sensor detects a temperature of 70°C or lower, the liquid bypass valve will be turned off. 25.15. Emergency operation
When the emergency operation switch (DSW1) on the outdoor unit printed circuit board is set to emergency, the emergency operation is enabled. This allows normal operation to continue, with all abnormalities other than a discharge temperature abnormality, high pressure abnormality or overcurrent abnormality being ignored.
25.16. DIP switch settings - Indoor unit printed circuit board (DSW1)