Adjust the main bracket position. Insert the B block in the CN4001 and the CN4003 on the A board.
You need to rewrite the service mode status so that the input adaptor can accept HD SDI signals. The following shows how to do this.
3
Press the MENU/EXIT and ENTER/SELECT buttons as needed to display �SDI EXIST 0 216� on the screen.
MENU SELECT
B block
1
Press the MENU/EXIT button on the monitor. The main menu appears.
MENU
EXIT MENU
COLOR TEMP ADJ... INPUT CONFIG... SYSTEM CONFIG... SERIAL REMOTE...
ENTER
SDI EXIST
0 216
EXIT
SELECT ENTER
MENU
A board CN4003 CN4001
After Installing the Input Adaptor
2
1 9
Connect the IN/MONITOR OUT plug (BNC connector installed in Step 5) to the IN/OUT (B block connector).
Return the G board installed in Step 5 in �Before Installing the Input Adaptor� to the original location. Lock the board with the two screws.
To go to the service mode, press the DEGAUSS and ENTER/ SELECT buttons at the same time. The service mode status menu appears.
SELECT
4
Using the +/� button, change �0� to �1� in �SDI EXIST 0 216.�
RESET
2
Reconnect the cables removed in Step 3 in �Before Installing the Input Adaptor�. Slide the main bracket back into the unit until it is set in the original place. Insert the fan connector removed in Step 1 in �Before Installing the Input Adaptor� into the monitor connector. Use the screws (12) to install the rear cover of the monitor.
Note
DEGAUSS
BTA 1125 N/S H. SIZE 238 3
ENTER
SDI EXIST 1 216
3
5
Press the DEGAUSS button. The �WRITE� message appears.
10Connect the cable (red/yellow/
black) from the B block fan to the CN 3 connector on the GC board.
You cannot turn on the power unless you connect the fan connector.
Note
DEGAUSS
SDI EXIST 1 216 WRITE
Reinstall the components and cables just as they were before installation was begun.